TECHNICAL SPECIFICATIONS
|
PRIMARY SUPPLY VOLTAGE – IN |
230 +10% -15% V AC |
|
PRIMARY SUPPLY VOLTAGE/ CURRENT – OUT |
0.5 A @ 28.5 V DC nominal (max.) |
|
SECONDARY SUPPLY VOLTAGE |
21.0 min. – 27.2 max.V DC – BAT charger o/p 28 V DC |
|
INTERNAL BATTERY CAPACITY – MAXIMUM |
2 x 12 V x 1.2 Ah Sealed VRLA Lead Acid Batteries |
|
MAINS FUSE/ BATTERY FUSE |
1 A -250 V Slow Blow – 20 mm/ 1.0 Amp – Resettable |
|
ZONE CURRENT – QUIESCENT/ ALARM |
4 mA / 65 mA |
|
MAX. CABLE RESISTANCE/ CAPACITANCE |
40 Ohms / 0.470 uF |
|
END OF LINE MONITORING |
Active EOL – 10uF/50V Bipolar Electrolytic Aluminium Capacitor |
|
BS5839 DETECTOR REMOVAL COMPLIANT |
YES provided diodes are fitted to detector base |
|
DEVICES PER ZONE |
32 Maximum – EN 54-2 |
|
ALARM RESISTANCE VALUE |
270 – 1000 Ohms |
|
SOUNDER CIRCUIT SPECIFICATION |
1 output w/ 300 mA max. current drive – fully monitored |
|
ALARM VOLTAGE/ END OF LINE RESISTOR |
27.5 V DC Nominal / 10 K Ohms – 1/4 Watt E.O.L. |
|
OPERATING TEMPERATURE / MAX. HUMIDITY |
-10ºC to 50ºC / 95% RH Non-Condensing |
|
WEIGHT |
1.1 Kg – 2.3 Kg (inc. 2 x 1.2 AH 12 V bat.) |
|
DIMENSIONS |
194 (L) x 256 (W) x 86 (H) mm |
|
COLOUR |
White or Red |